Viewed 2204 Times 0 Comments

The PFC (Like all elnet products) has an automated swap of the current line – to solve mistake of wiring (L<->K).

So – when using generator it automatically set the sign to be correct.

You can use the PFC in generator without any problem.

Normally user decide NOT to use the PFC in generator mode. In this case you can use the different SetPoint by using Digital in – so when the generator is on (it switch digital in) – and you choose a lower setpoint in this mode – and the PFC will stop to connect capacitors.

Was this answer helpful ? Yes (0) / No (0)